DBM 610 Airflow Meter

Brand: Kimo Instruments

DBM 610 Airflow Meter

Brand: Kimo Instruments
Specifications
  • Measuring range from 40 to 3500 m3/h
  • Quick and simple hood changes 
  • Software for data processing on computer
  • Sturdy, lightweight and easy to handle
  • Removable measuring unit
  • Interchangeable hoods
  • Simultaneous display of airflow and temperature
  • Automatic airflow direction (extraction or air blast)
  • Automatic averaging or point by point averaging
  • HOLD function
  • Removable measuring unit(micromanometer function)
  • Data processing on computer with USB port
  • Different languages available

Specifications

Airflow

  • Measuring Range: From 40 to 3500 m³/h
  • Accuracy: 3 % of the measurement ± 10 m³/h
  • Resolution: 1 m³/h

Air Velocity

  • Measuring Range: From 0.2 to 10 m/s
  • Accuracy: ± 3 % of the measured value ± 0.04 m/s
  • Resolution: 0.01 m/s up to 3 m/s and 0.1 m/s above

Temperature (On the Base)

  • Measuring Range: From 0° to 50° C
  • Accuracy: 2 % of the measured value ± 0.1° C
  • Resolution: 0.1° C

Temperature Thermocouple (On the Micromanometer)

  • Thermocouple  Type: K, J, T, S
  • Measuring Range: K : from -200° to 1300° C
  • Measuring Range: J : from -100° to 750° C
  • Measuring Range: T : from -200° to 400° C
  • Measuring Range: S : from 0° to 1760° C
  • Accuracy: K, J, T : from -200° to 0° C : ± 0.4° C ± 0.3 % of Reading, from 0° to 1300° C : ± 0.4° C
  • Accuracy: S : ± 0.6° C
  • Resolution: 0.1° C

Pressure

  • Measuring Range: From -2500 to +2500 Pa
  • Accuracy: ± 0.2 % of Reading ± 2Pa
  • Resolution: From 0.001 to 0.1 Pa

Display

  • Large graphic back-lighted LCD / Sizes : 86 x 51 mm

Connectors

  • ABS connectors, Ø 7 x 4 mm

Storage Capacity

  • 200 datasets of 100 points

Housing

  • Shock-proof made of ABS, IP54 protection

Keypad

  • 12 keys

Conformity

  • Electromagnetical compatibility (NF EN 61326-1 guideline)

Power Supply

  • 4 alkaline batteries LR6
  • Rechargeable battery Li-ion 3.7 V 4400 mhA (optional)

Environment

  • Neutral gases

Operating Temperature

  • From 0° to +60° C

Storage Temperature

  • From -20° to +70° C

Auto-Shut-Off

  • Adjustable from 0 to 120 min

Weight

  • 3600 g

Languages

  • French, English, German, Finnish, Dutch, Italian, Norwegian, Portuguese, Slovak, Swedish, Chinese

Models matching criteria: 13
DBM 610 Airflow Meter view more
DBM 610 : 
  • 610 x 610 mm hood
  • Pitot tube length 300 mm
  • 2 x 1 m of silicone tube
  • USB cable
  • Calibration certificate
  • Transport case
Out of Stock
DBM 610 Airflow Meter view more
DBM 610 C : 
  • 5 hoods 
    • 610 x 610 mm
    • 720 x 720 mm
    • 720 x 1320 mm
    • 420 x 1520 mm
    • 1020 x 1020 mm
  • Pitot tube length 300 mm
  • 2 x 1 m of silicone tube
  • USB cable
  • Calibration certificate
  • Transport case
Out of Stock
Measurement Grid Kit for DBM 610 Instrument view more
Designed for air velocity measurements on any types of large celling vent or diffuser. 

The grid is similar to the DBM610 grid. It calculates the average air velocity from 24 points to guarantee a reliable measurement.. 

The grid is attached to a telescopic (maximum length is 2.05 m) and articulated pole (from 0 to 90°). 

Struts of 3 different lengths allow a correct positioning of the grid on the celling surface.

A bagpack allows easy carriage of the grid and its accessories (telescopic pole, articulation, 2 x 2.5 m of silicone tube, positioning struts and electronic housing).

  • Measuring range 
    • from 0.2 to 10 m/s
  • Accuracy 
    • ±3 % of the measured value ±0.04 m/s
  • Resolution 
    • 0.01 m/s up to 3 m/s and 0.1 m/s beyond
  • Struts length 
    • 5 cm / 15 cm / 25 cm
Out of Stock
DBM 610 Airflow Meter view more
Saving and visualization of measurements datasets software
Out of Stock
Lithium Battery with Power Supply Adapter
Out of Stock
Alone Removable Unit view more
Range from 40 to 3500 m3/h / -2500 Pa to 2500 Pa, micromanometer function : measurement of air velocity and airflow with different differential pressure instruments (Pitot tube, Debimo), compensation of the measurement according to thermocouple temperature. 

Supplied with 2 x 1 m of silicone tube and calibration certificate
Out of Stock
Transport Case for DBM 610 Instrument and Hoods
Out of Stock
610 x 610 mm Hood
Out of Stock
720 x 720 mm Hood
Out of Stock
720 x 1320 mm Hood
Out of Stock
420 x 1520 mm Hood
Out of Stock
1020 x 1020 mm Hood
Out of Stock
Set of 4 Fiber Rods, for DBM610
Out of Stock

Documentation

show more