Accuracy
- Maximum
- Typical Linearity: ± 0.01 %
Ambient Temperature Range
- 0° to 70° C (32° to 158° F)
Approvals & Certifications
- CE
- EMC BS EN 61326
- UL 94-VO
- VDE 0304 Part 3, Level IIIA
Electrical Protection
- Reverse Connection Plus Overvoltage
Humidity
- 10 to 95 % Relative Humidity, Non-Condensing
Input
- Offset: -20 mV - 40 V
- Span: 20 mV - 100 V
Isolation
- 500 Vdc (Flash Tested to 1 kV)
Mounting
- Rail Mounting Snap on Top Hat (DIN EN 50022-35)
Output
- 4-20 mA, 30 mA - Max.
- Ripple: less than 40 µA/V
Response Time
- 200 milliseconds to Reach 70 % of Final Value
Size
- Cable Size: 4 mm² Solid / 2.5 mm² Standard