SEM1636 Signal Conditioner/Trip Amplifier

Brand: Status Instruments

SEM1636 Signal Conditioner/Trip Amplifier

Brand: Status Instruments
The SEM1636 monitors a (4 to 20) mA loop and provides two independent change over trip contacts set to alarm at any point within the (4 to 20) mA range. 

The SEM1636 requires no additional power connection as power is derived from the (4 to 20) mA loop. Relay outputs are independently configured for action and set point, dead band. 

Six actions are provided normal High/Low/Deviation and inverted High/Low/Deviation. Additional math, filter and user linearisation functions are provided.
Features
  • Dual Change Over Relay Output
  • Relay Rating 250V AC 1A; 30V DC 1A
  • Latching Relays In Case Of Loop Failure
  • Powered From 4/20mA Loop
  • LED Alarm Indication
  • View Live Data On An Android Phone Or Tablet

Specifications

Accuracy

  • ± 0.02 % of Full Scale Deviation

Ambient Temperature Range

  • Configuration Ambient: 10° to 30° C (50° to 86° F)

Approvals & Certifications

  • CE: BS EN 61326 BS EN 61010-1 Installation Category II Pollution Degree

Circuit Protection

  • Protect with Externally Fitted 2 A (T) Fuse: Relay 1 & Relay 2
  • Reverse Connection & Overvoltage: Relay 1

Communication

  • Baud Rate: 19,200 bit/sec
  • USB 2.0

Configuration

  • USB Port

Connection Style

  • Screw Terminals 2.5 mm, Max.

Electrical Connectors

  • DIN 43880

Electrical Contacts

  • Form C Relay Contacts: Relay 1 & Relay 2

Electrical Rating

  • 250 Vac RMS at 1 A: Relay 1 & Relay 2
  • 30 Vdc at 1 A Resistive Load: Relay 1 & Relay 2

Environmental Protection

  • IP65 - DIN Rail Enclosure Offering Protection

Function

  • Linear
  • Math Function

Humidity

  • 10 to 90 % Relative Humidity, Non-Condensing

Indication

  • LED

Input

  • ± 50 mA - Max.
  • 3.8-22 mA - Operating
  • 4-20 mA - Current Loop
  • 5 V, Max.

Isolation

  • 3,750 Vac Relay 1 to Inputs, Relay 1 to Relay 2

Materials of Construction

  • Polyamide 6.6 Self Extinguishing

Mounting

  • DIN Rail

Operating Temperature

  • -20° to 70° C (-4° to 158° F)

Storage Temperature

  • -30° to 70° C (-22° to 158° F)

System Requirements

  • Windows® XP

Temperature Coefficient

  • ± 0.002 %/°C

Time Constant

  • Filter: 0 to 100 seconds

Update Time

  • 100 milliseconds
show more