SEM1600T Signal Conditioner
Brand: Status InstrumentsSEM1600T Signal Conditioner
Brand: Status InstrumentsThe SEM1600T accepts resistance or mV signals from RTD, Slidewire or Thermocouple sensors.
The flexible design allows the use of any resistive sensor within the range of (10 to 10,500) Ohms.
Including Pt100, 500, 1000, Ni or Cu sensors, slide wire sensors up to 100 KiloOhms and 13 different thermocouple types.
Other sensor characteristics or your own 22 point linearisation characteristic (for slidewire, linear resistance or mV) can be downloaded into the product enabling you to adapt it exactly to your application.
Features- Current, Voltage or Bipolar Voltage Output
- Powered 10-32 Vac / 10-48 Vdc Supply
- 22 Segment User Linearisation
- Sensor Offset and Output Alignment
- Adjustable Input Filter
Specifications
Brand
Accuracy
- (mA Output/2,000) or 5 µA whichever is greater, Drift 1 µA/°C
- Cold Junction: ± 0.2° C (± 0.36° F), ± 0.05° C/°C
- Output Voltage: ± 5 mV
- Sensor Thermocouple: ± 0.1 % of Full Scale ± 0.5° C - Input Typicals: R, S/Input Typicals: K, J, E, N, L, U, B, C, D, W (Plus Sensor Error)
- Sensor Thermocouple: ± 0.2 % of Full Scale ± 0.5° C - Input Typical: T (Plus Sensor Error)
- Sensors RTD: 0.2° C + (°0.05 % of Reading) (Plus Sensor)
- Thermocouple mV Input: ± 0.02 % of Full Scale
Ambient Temperature Range
- 10° to 30° C (50° to 86° F)
Approvals & Certifications
- BS EN 61326
- CE
- IEC
Communication
- Baud Rate: 19,200 bit/sec
Current
- Current Drive: ± 2 mA (Min. Load 5000 ohms at 10 V) - Output Voltage
- Current Sink (Range): 0-21.5 mA - Output Current
- Excitation Current: < 200 μA - Resistance RTD Input
Electrical Connectors
- DIN 0.00618
- DIN 43880
Environmental Protection
- IP65
Humidity
- 10 to 90 % Relative Humidity, Non-Condensing
Indication
- Green LED (When Output (-0.1 to 100.1 %) Else Red
- Red LED (Input/Output Error)
Input
- -100 to 200 mV
Interface Connection
- USB 2.0
Isolation
- Galvanic: 500 Vdc (Supply to Input to Output)
Load
- 5,000 ohms at 10 V (Min.)
Materials of Construction
- Polyamide 6.6
Mounting
- DIN Rail
Operating Temperature
- -30° to 70° C (-22° to 158° F)
Output
- 0 to 10.1 V
- -10.1 to 10.1 V
Output Load
- 750 ohms, Max.
Power
- < 1 W Full Power
Power Supply
- 10-30 Vdc
Power Supply Effect
- 0.2 μA/V
Resistance
- 10 to 500 ohms ± 0.055 ohms
- 2,500 to 10,500 ohms ± 10.0 ohms
- 500 to 2,500 ohms ± 0.5 ohms
- Maximum
Response Time
- 400 milliseconds
RTD Type
- Cu100
- Cu1000
- Cu53
- Ni100
- Ni1000
- Ni120
- Ni507.5
- Ni604
- Pt100
- Pt1000
- Pt500
Sensor, Probe Material
- Copper
- Nickel
- Platinum
- Silicon
Sensor, Probe Type
- B Thermocouple
- C(W5) Thermocouple
- D(W3) Thermocouple
- E Thermocouple
- G(W) Thermocouple
- J Thermocouple
- K Thermocouple
- L Thermocouple
- N Thermocouple
- RTD
- R Thermocouple
- S Thermocouple
- T Thermocouple
- U Thermocouple
Storage Temperature
- -30° to 70° C (-22° to 158° F)
Supply Voltage
- 10-32 Vac Protected by Internal 500 mA Resettable Fuse
- 10-48 Vdc
System Requirements
- Windows® XP
Temperature Range
- Cold Junction: -40° to 85° C (-40° to 185° F)
- Thermocouple: -200° to 2,300° C (-328° to 4,172° F)
Thermal Drift
- (0 to 500 ohms) 0.013 ohms/ °C
- (2,500 to 10,500 ohms) 0.27 ohms/°C
- (500 to 2,500 ohms) 0.063 ohms/°C
- 0.05° C/°C of Span
- 1 μA/°C
- Thermocouple Offset: 0.1° C/°C
Turn-On Time
- 5 seconds
Update Time
- 300 milliseconds
- Warm-Up: 2 minutes