SEM1630 Trip Amplifier
Brand: Status InstrumentsSEM1630 Trip Amplifier
Brand: Status InstrumentsThe SEM1630 is the new generation DIN Rail Mounted Trip Amplifier from Status Instruments.
It has been designed to accept most common process and temperature sensor inputs and provide the user with a dual trip output.
Isolation is provided on all three ports. All temperature ranges are linear to temperature.
Designed for ease of use, our latest USB interface is fitted for quick and easy configuration. Just connect a standard USB cable between the SEM1630 and your PC.
Using our free configuration software, your PC will automatically upload the existing configuration data and guide you through any changes you wish to make.
Features- Pt100, Thermocouple, mA, mV input
- Dual Relay Outputs 250V AC @ 1A
- Relay Contacts isolated from each other
- Galvanic Isolation
- View Live Data On An Android Phone Or Tablet
Specifications
Brand
Accuracy
- ± 0.008 mA - Input Typical: mA
- ± 0.04 mV - Input Typical: mV
- ± 0.1° C (± 0.2° F) + (± 0.05 % of Reading) - Input Typical: Pt100
- ± 0.5° C (± 0.9° F) ± 0.1 % of Full Scale Range, Only over the Range 800° to 1,600° C (1,472° to 2,912° F) - Input Typical: R, S
- 0.1 % of Full Scale Range ± 0.5° C (± 0.9° F) - Input Typical: K, J, E, N
- 0.2 % of Full Scale Range ± 0.5° C (± 0.9° F) - Input Typical: T
Ambient Temperature Range
- -10° to 50° C (14° to 122° F)
Approvals & Certifications
- CE Tested to BS EN 61326
Cable Length
- 0.09” (2.5 mm) - Max.
Circuit Protection
- Over-Voltage
Configuration
- USB Port
Current
- ± 100 mA - Max.
- 100 mA - Max.
Electrical Connectors
- Screw Terminal
Electrical Rating
- 250 Vac at 1 A
- 30 Vdc at 1 A
Humidity
- 10 to 95 % Relative Humidity, Non-Condensing
Input
- Isolated
- Pt100
Input Impedance
- 1 Megaohm - Not Including 0.2 µA Open Circuit Detect Bias Current Effect
- 2.7 ohms - Input Typical: mA
Isolation
- 3,750 Vac - Galvanic
Materials of Construction
- Polyamide 6.6 Self Extinguishing
Mounting
- DIN Rail Mounting
Operating Temperature
- -20° to 70° C (-4° to 158° F)
Output Format
- Dual Form C Relay Contact
Relay Output
- Dual: 250 Vac at 1 A
Resistance
- Maximum
Resistance Effect
- Lead Effect: 0.015° C/ohms
Response Time
- < 500 milliseconds to Reach 95 % of Final Value
Sensor Excitation
- < 450 µA
Sensor, Probe Type
- E Thermocouple
- J Thermocouple
- K Thermocouple
- N Thermocouple
- Pt100
- R Thermocouple
- S Thermocouple
- T Thermocouple
Stability
- ± 0.005 % of Full Scale Range/°C
- ± 0.01 % of Full Scale Range/°C
Storage Temperature
- -40° to 85° C (-40° to 185° F)
Supply Voltage
- 24 Vdc ± 5 % @ 40 mA - Max.
Temperature Effect
- 0.015° C/ohms - Lead Effect
Temperature Range
- -20° to 70° C (-4° to 158° F) - Cold Junction
- -200° to 1,760° C (-328° to 3,200° F)
Turn-On Time
- Start Up Time < 3 seconds