SEM203P Temperature Transmitter

Brand: Status Instruments

SEM203P Temperature Transmitter

Brand: Status Instruments
The SEM203/P is a low cost configurable in-head transmitter that accepts PT100 temperature sensors and converts sensor output over a configured range to a standard industrial (4 to 20) mA transmission signal. 

A simple push button operation allows the user to not only select the desire range and burnout direction but also perform user trim at both (4 and 20) mA points. 

The SEM203 in head transmitter incorporates the latest digital technology to ensure accurate drift free performance. 

If required the desired range can be specified at the time of order, removing the need for user configuration. 

If the range is not specified then the transmitter will be shipped with the default range of (0 to 100) ° C set.

Specifications

Accuracy

  • (mA Output/2,000) or 5 μA whichever is greater
  • Measurement Accuracy: 0.2° C (0.36° F) ± 0.05 % of Reading

Ambient Temperature Range

  • -40° to 85° C (-40° to 185° F)

Approvals & Certifications

  • EMC - BS EN 61326
  • IEC 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5

Circuit Protection

  • Surge

Configuration

  • Unique Push Button

Current

  • < 200 µA - Excitation Current

Humidity

  • Ambient Humidity: 10 to 90 % Relative Humidity, Non-Condensing

Linearization

  • BS EN 60751 (IEC 751) Standard / JISC 1604

Output

  • < 3.9 mA - Min.
  • 21.5 mA - Max.
  • 4-20 mA, 2-Wire Current Loop

Output Load

  • Maximum

Power Supply

  • 10-30 Vdc

Power Supply Effect

  • Loop Voltage Effect: 0.2 µA/V

Resistance

  • Maximum

Response Time

  • 1 second

Sensor Protection

  • Programmable Burn-Out

Sensor, Probe Connection

  • Screw Terminal

Sensor, Probe Type

  • Pt100 100R @ 0° C 2- or 3-Wire

Span - Minimum

  • 25° C (77° F)

Storage Temperature

  • -50° to 90° C (-58° to 194° F)

Temperature Effect

  • 0.002° C/ohm - Lead Resistance

Temperature Range

  • Sensor Range: -195° to 845° C (-319° to 1,553° F), (18 to 390) ohms

Thermal Drift

  • ± 0.02° C/°C
  • ± 2 μA/°C

Turn-On Time

  • Start Up Time: 4 seconds (I Out < 4 mA During Start Up)

Update Time

  • 500 milliseconds
  • Warm-Up Time: 1 Minute to Full Accuracy

show more