Sensor
- Thermocouple type K, J, T and N
Connection
- 2 wires passive transmitter
Measuring Range
- Thermocouple K: -200° C…+1200° C
- Thermocouple J: -200° C…+800° C
- Thermocouple T: -200° C…+300° C
- Thermocouple N: -200° C…+1200° C
Linearization
- EN 60584-1-2
- ASTM E 230 - ANSI (MC96-1)
Default Range
- Tc = K - Range = 0…1000° C
Accuracy
- ± 0.04 %FS ± 0.04 % of the reading or 0.5° C (the greater of the two values)
Operating Temperature of the Cold Junction
Type of Output
- 4…20 mA (or 20…4 mA) two wires 22 mA if sensor is broken or not connected
Resolution
- 4 μA Display: 0.1° C T200° C, 1° C T > 200° C
Power Voltage
- 9…30 Vdc (protection against polarity inversion)
Sensitivity to Vdc Power Voltage Variations
Load Resistance
- RLMax. = (Vdc-9)/0.022
- RLMax. = 680 Ω with Vdc = 24 Vdc
Input/Output Galvanically Insulation
- 50 Vdc (verified at 250 V)
Red Led
- It turns on while programming, when the probe is broken or not connected