Accuracy
- (mA Out x 0.0005) or 5 µA whichever is greater
Ambient Temperature Range
- 0° to 50° C (32° to 122° F)
Approvals & Certifications
- EMC - BS EN 61326
- IEC 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5
Electrical Connectors
- M20
- Output Connection: Two Part Screw Terminal
- Solid/Stranded Wire: 20 to 28 AWG
Humidity
- 0 to 100 % Relative Humidity
- Transmitter: 10 to 90 % Relative Humidity, Non-Condensing
Length
- Wire Strip Length: 6 to 7 mm
Mounting
- Duct Mount
- Remote Mounting
- Wall Mounted
Operating Temperature
- Probe: -30° to 100° C (-22° to 212° F)
- Transmitter: -30° to 85° C (-22° to 185° F)
Output
- 4-20 mA, 2-Wire Current Loop
- Maximum
- Minimum 3.9 mA (In Low Burn-Out Condition)
Power Supply
- 10-30 Vdc
- 15-30 Vdc with Display
Power Supply Effect
- Loop Voltage Effect: 0.2 µA/V
Resolution
- 0.1 % at 0.1° C / 32.18° F
Sensor, Probe Type
- Sensor: Humidity/Temperature
Stem Length
- 4.33” to 197” (110 to 5,000 mm)
Storage Temperature
- Transmitter: -50° to 90° C (-58° to 194° F)
System Requirements
- USB Configurator
- Windows® XP or Later
Temperature Range
- -30° to 100° C (-22° to 212° F)
Turn-On Time
- Start Up Time: 10 seconds
Update Time
- 3 seconds
- Display: 800 milliseconds