SEM1600VI Signal Conditioner
Brand: Status InstrumentsSEM1600VI Signal Conditioner
Brand: Status InstrumentsThe SEM1600VI is a “smart” powered isolator/conditioner that accepts any voltage signal between (-50 and 50) Vdc or any current signal between (-50 and 50) mA.
The output stage offers either voltage, bipolar voltage or current re-transmission signals.
The retransmission signal can be ranged to a scale anywhere within the input process range.
A transmitter power supply is provided on both input and output meaning the products can accept sink or source applications.
There are a number of free software tools available including 22 segment user linearisation / profiling, maths functions and input signal damping. These enable you to configure the product exactly to your requirements.
Features- Accepts Internal and External Powered Current Loops On Input and Output
- +/- 50V DC or 50 mA Input
- Current, Voltage Or Bipolar Voltage Output
- Powered ( 10 to 32) V AC / (10 to 48) V DC Supply
- 22 Segment User Linearisation
- View Live Data On An Android Phone Or Tablet
Specifications
Brand
Accuracy
- Current Input: -22 to 22 mA ± 5 µA
- Current Input: -50 to 50 mA ± 10 µA
- Output Current: (mA Out/2,000) or ± 5 µA whichever is greater
- Output Voltage: ± 5 mV
- Voltage Input: -22 to 22 V ± 5 mV
- Voltage Input: -50 to 50 V ± 10 mV
Ambient Temperature Range
- 10° to 30° C (50° to 86° F)
Approvals & Certifications
- CE - BS EN 61326
Communication
- Baud Rate: 19,200 bit/sec
- USB 2.0
Current
- Current Drive: ± 2 mA
- Current Source & Sink: 0-21.5 mA
Damping Adjustment
- 0 to 3,600 seconds
Electrical Connectors
- DIN 43880
- Terminals 2.5 mm, Max.
Environmental Protection
- IP65
Humidity
- 10 to 90 % Relative Humidity, Non-Condensing
Indication
- LED - (Green when Output -0.1 to 100.1 %), (Red = Input/Output Error)
Input
- -50 to 50 mA
- -50 to 50 V
Input Impedance
- Current Input: < 30 ohms
- Voltage Input: 1 Megaohm
Isolation
- Supply to Input to Output 500 Vdc
Materials of Construction
- Polyamide 6.6
Mounting
- DIN Rail
Operating Temperature
- -30° to 70° C (-22° to 158° F)
Output
- 0 to 10.1 V
- -10.1 to 10.1 V
Output Load
- Current Source: Max.
- Minimum 5,000 ohms at 10 V
Power
- < 1 W Full Power
Power Supply
- 10-32 Vac Protected by Internal 500 mA Resettable Fuse
- 10-48 Vdc
Power Supply Effect
- Current Sink: 0.2 µA/V
Response Time
- 400 milliseconds
- Update 300 milliseconds
- Warm-Up 2 minutes
Storage Temperature
- -30° to 70° C (-22° to 158° F)
Supply Voltage
- Current Sink: 10-30 Vdc
System Requirements
- USB Configurator
- Windows® XP
Thermal Drift
- < ± 0.01 % of FSD/°C
- 1 μA/°C
Turn-On Time
- 5 seconds