Accuracy
- Cold Junction Error: ± 0.5° C (± 0.9° F)
- Cold Junction Tracking: 0.05° C/°C
- Current Input: 0.05 % of Full Scale ± 0.05 % of Reading
- Isolated Re-Transmission: 0.07 % of Full Scale
- RTD: 0.1° C (32.18° F) ± 0.05 % of Reading
- Voltage Input / RTD: ± 0.04 % of Full Scale or ± 0.04 % of Reading or ± 0.5° C (32.9° F), whichever is greater
Alarm
- High/Low
Approvals & Certifications
- EMC BS EN 61326, BS EN 61010-1
- IEC707 FVO
- UL 94VO
Communication
- 4-Wire or 2-Wire Half-Duplex RS-485
- RS-485 Modbus Communication Protocol
Consumption
- Power Consumption: 10 VA (Worst Case) 6 VA Typical
Current
- 0 to 23 mA
- Excitation Current: 1 mA
- Ripple Current: < 3 µA
Electrical Connectors
- 5-Way Tension Clamp Connector
- Termination: Screw Terminal
Electrical Contacts
- 2 × Changeover Relays with Common Wiper
Environmental Protection
- IP65
Frequency
- 50/60 Hz
Humidity
- 10 to 90 % Relative Humidity
Input
- ± 10 mA
- ± 100 mV
- ± 20 mA
- -10-10 V
- 4-20 mA
Input Impedance
- 1 Megaohm - Voltage
- 20 ohms - Current
Interface Connection
- 8 Way RJ45 Connector (Supplied with Matching Plug & 1 Meter Cable)
Isolation
- 500 Vac
Load
- Dual Relay Alarm / Pulse - AC, Maximum
- Dual Relay Alarm / Pulse - DC, Maximum
Materials of Construction
- ABS/PC
Operating Temperature
- -30° to 60° C (-22° to 140° F)
Operating Temperature - Sensor
- -200° to 850° C (-328° to 1,562° F)
Operation
- Electrical Life: 100,000 Operations at Rated Load
- Mechanical Life: 50 Million Operations
Output
- 0-10 V
- 0 to 100 mA (Active or Passive) - Isolated Re-Transmission
Output Load
- Active: Maximum
Power
- Dual Relay Alarm / Pulse - AC, Maximum
- Dual Relay Alarm / Pulse - DC, Maximum
Power Supply
- 20-35 Vdc
- 90-264 Vac (50 to 60) Hz
Power Supply Effect
- Voltage Effect: 0.2 μA/V
Resistance
- 50 ohms/Leg - Maximum
Resistance Effect
- 0.002° C/ohms - Lead Resistance Effect
RTD Type
- Ni120
- Pt100
Sensor, Probe Type
- B Thermocouple
- E Thermocouple
- J Thermocouple
- K Thermocouple
- L Thermocouple
- N Thermocouple
- RTD
- R Thermocouple
- S Thermocouple
- T Thermocouple
Span - Minimum
- > 10 % of Range
Stability
- 1 µA/°C
Storage Temperature
- -50° to 85° C (-58° to 185° F)
Supply Voltage
- 30 V (Passive Mode) - Maximum
Temperature Range
- Cold Junction Range: -20° to 60° C (-4° to 140° F)
Thermal Drift
- Current Input: 0.02 %/°C
- RTD - Span: 0.002 %/°C
- RTD - Zero: 0.004 ohms/°C
- RTD - Zero: 4 µV/°C
- Voltage Input / RTD Span: 0.01 %/°C
Voltage
- Dual Relay Alarm / Pulse - AC, Maximum
- Dual Relay Alarm / Pulse - DC, Maximum